Comparison

Induction Motor vs Synchronous Motor

A 1500 rpm nameplate on an induction motor in India means the rotor actually turns at 1440–1480 rpm — it slips behind the rotating field and that slip is what creates torque. A synchronous motor's rotor locks to the field and runs at exactly 1500 rpm regardless of load — that same locking mechanism allows it to supply reactive power to the grid like a capacitor bank. The choice between them hinges on whether you want simplicity or power factor correction.

EEE

Side-by-side comparison

ParameterInduction MotorSynchronous Motor
SpeedN = Ns(1 – s); always less than synchronous speed (slip 2–5%)N = Ns = 120f/P exactly; runs at synchronous speed always
SlipNon-zero — slip creates rotor current and torqueZero at steady state — rotor locked to field
Self-StartingYes — starts and accelerates to near-synchronous speedNo — needs damper windings or auxiliary motor to start
Power FactorAlways lagging (0.8–0.9 lagging typical); cannot be variedAdjustable: leading, unity, or lagging by varying DC excitation
DC ExcitationNot requiredRequired for rotor field (separately excited with DC)
HuntingDoes not hunt — no synchronizing torqueHunts if load suddenly changes; damper windings reduce hunting
Efficiency92–96% at full load for large motorsSlightly higher at large ratings; no slip loss
ApplicationPumps, fans, compressors, conveyors — general industrial drivesPower factor correction, constant-speed loads: synchronous condensers, large compressors above 1 MW

Key differences

Induction motors slip behind synchronous speed — a 4-pole, 50 Hz motor has Ns = 1500 rpm but runs at 1440 rpm under full load (slip = 4%). That slip is essential: without it, no current would be induced in the rotor and no torque would develop. Synchronous motors run at exactly Ns = 120f/P — a 6-pole, 50 Hz synchronous motor locks at 1000 rpm. They cannot start on their own (rotor has no induced currents at standstill) and need damper windings for run-up. Over-excitation makes synchronous motors draw leading current, effectively acting as capacitor banks — synchronous condensers in substations exploit this for reactive power compensation.

When to use Induction Motor

Use an induction motor for any self-starting, variable-load industrial application — for example, a 75 kW, 415 V, 3-phase squirrel cage induction motor on a centrifugal pump in a chemical plant.

When to use Synchronous Motor

Use a synchronous motor when you need exactly constant speed, power factor correction, or both — for example, a 2 MW, 11 kV synchronous motor driving a large air compressor in a steel plant while simultaneously correcting the plant power factor from 0.75 to 0.95 leading.

Recommendation

For exam problems, choose induction motor when self-starting is required and power factor correction is not mentioned. Choose synchronous motor when the question mentions leading power factor, synchronous condenser, or exact speed. That pair of conditions resolves most motor-selection exam questions.

Exam tip: Examiners ask why synchronous motors cannot start on their own — explain that at standstill the rotor cannot follow the rapidly rotating stator field (50 Hz = 3000 rpm for 2-pole), so no net torque develops; damper windings provide asynchronous starting torque.

Interview tip: Interviewers at power plants ask about V-curves of synchronous motors — explain that the graph of armature current vs. field current is V-shaped, with unity power factor at the minimum current point and leading/lagging on either side.

More Electrical Machines comparisons