Comparison

Symmetric vs Unsymmetric Fault

When a 220 kV transmission tower collapses and all three phases contact the ground simultaneously, every protective relay fires at once — that is a symmetric three-phase fault, the rarest but most severe event. When a single conductor snaps and touches earth on a 33 kV feeder in Uttarakhand, only one relay operates — that single-line-to-ground fault is unsymmetric and accounts for nearly 80% of all power-system faults. Choosing the right analysis method and relay setting depends entirely on which category you are dealing with.

EEE

Side-by-side comparison

ParameterSymmetricUnsymmetric Fault
Fault Type3-phase (LLL or LLLG) — balancedLG, LL, LLG — unbalanced
Frequency of Occurrence< 5% of all faults> 95%; SLG alone is ~65–70%
Symmetry of CurrentsAll three phase currents equal; 120° apartPhase currents unequal; negative/zero sequence appear
Analysis MethodSingle-phase equivalent (positive sequence only)Symmetrical components (Z1, Z2, Z0 networks)
Sequence Networks UsedPositive sequence onlyAll three: Z1, Z2, Z0 connected per fault type
Fault Severity (current magnitude)Highest — up to 20–25 kA at 220 kV busSLG fault current often lower (limited by Z0)
Zero Sequence CurrentZero (balanced — no neutral current)Present in LG and LLG; flows through earth/neutral
Relay ResponseDistance relay (21), overcurrent — all three phases tripEarth fault relay (50N/51N) for SLG; 67 for LL
Transformer Neutral Grounding EffectNot relevantZ0 path depends on neutral grounding; isolated neutral blocks earth fault current
Example ScenarioThree-phase bus fault at 220 kV substationSingle conductor touching tower at 33 kV feeder

Key differences

Three-phase faults produce the highest fault current (up to 25 kA at 220 kV) but are analysed with only the positive sequence network — no Z2 or Z0 needed. Single-line-to-ground faults require all three sequence networks in series: If = 3Ea/(Z1+Z2+Z0), making zero-sequence impedance critical. A solidly grounded system has low Z0 and produces high SLG current; an isolated neutral system has Z0 → ∞ and almost zero SLG current. Negative sequence current (present in all unsymmetric faults) heats generator rotors and triggers negative-sequence relays (46), which never operate during balanced faults.

When to use Symmetric

Use symmetric three-phase fault analysis when sizing circuit breakers and selecting equipment MVA ratings at substations. Example: a 220 kV bus at RRVPNL Heerapura is rated for a 40 kA symmetric short-circuit level determined by a 3-phase fault calculation.

When to use Unsymmetric Fault

Use unsymmetric fault analysis (symmetrical components) when setting earth-fault relays and studying power quality issues like negative-sequence heating. Example: a 33 kV feeder earth-fault relay (IDMT 50N, pick-up 10% of CT primary) is set based on the single-line-to-ground fault current calculated using Z0 of the delta–star transformer.

Recommendation

For equipment rating and breaker selection, always use the three-phase symmetric fault — it gives maximum current. For relay co-ordination involving earth faults and negative-sequence protection, choose unsymmetric fault analysis with symmetrical components. Both calculations are needed on any real project; they answer different questions.

Exam tip: Examiners ask students to calculate SLG fault current using If = 3Ea/(Z1+Z2+Z0) with given sequence impedances and then state what happens to this current if the neutral is isolated — zero, because Z0 becomes infinite.

Interview tip: A placement interviewer at a power consultancy will ask you to distinguish why a delta winding on a transformer blocks zero-sequence current — explain that delta provides no return path for zero-sequence, so Z0 seen from the delta side is infinite.

More Power Systems comparisons