Formula sheet

Transformer Formula Sheet

Transformer formulas are tested in every GATE Electrical Engineering paper and appear directly in industry practice — during a short-circuit test on a 100kVA distribution transformer, the per-unit leakage impedance determines the fault current that protection relays must interrupt. This sheet covers the EMF equation, equivalent circuit parameters, efficiency at maximum loading conditions, voltage regulation, and the open-circuit and short-circuit test procedures.

EEE

EMF Equation and Turns Ratio

Transformer EMF Equation

E = 4.44 \, f \, N \, \Phi_m

SymbolDescriptionUnit
ERMS EMF inducedV
fSupply frequencyHz
NNumber of turnsturns
ΦmMaximum flux in coreWb

Worked example

A single-phase transformer has 500 primary turns, connected to 230V 50Hz supply. Find the maximum core flux.

Given: E1=230V, f=50Hz, N1=500

  1. E = 4.44 * f * N * Φm
  2. Φm = E / (4.44 * f * N)
  3. = 230 / (4.44 * 50 * 500)
  4. = 230 / 111,000
  5. = 2.07 × 10^{-3} Wb
  6. = 2.07 mWb

Answer: Φm = 2.07 mWb

Turns Ratio

a = \frac{N_1}{N_2} = \frac{E_1}{E_2} = \frac{V_1}{V_2} = \frac{I_2}{I_1}

SymbolDescriptionUnit
aTurns ratio (primary to secondary)
N1, N2Primary and secondary turnsturns
I1, I2Primary and secondary currentsA

Worked example

A 230V/115V transformer has N1=800 turns. Find N2 and the current ratio when I1=5A.

Given: V1=230V, V2=115V, N1=800, I1=5A

  1. a = V1/V2 = 230/115 = 2
  2. N2 = N1/a = 800/2 = 400 turns
  3. I2/I1 = N1/N2 = a → I2 = a * I1 = 2 * 5 = 10A

Answer: N2 = 400, I2 = 10A

Impedance Transformation

Z_1 = a^2 Z_2, \quad Z_2' = a^2 Z_2

SymbolDescriptionUnit
Z1Impedance reflected to primary sideΩ
Z2Actual secondary-side impedanceΩ
Square of turns ratio

Worked example

A transformer has a=5. A 10Ω load on the secondary is reflected to the primary. Find Z_reflected.

Given: a=5, Z2=10Ω

  1. Z_reflected = a^2 * Z2
  2. = 5^2 * 10
  3. = 25 * 10
  4. = 250Ω

Answer: Z_reflected to primary = 250Ω

Equivalent Circuit Parameters

Approximate Equivalent Circuit Referred to Primary

R_{eq1} = R_1 + a^2 R_2, \quad X_{eq1} = X_1 + a^2 X_2

SymbolDescriptionUnit
R1, R2Primary and secondary winding resistancesΩ
X1, X2Primary and secondary leakage reactancesΩ
Req1, Xeq1Total resistance and reactance referred to primaryΩ

Worked example

A transformer: R1=0.5Ω, X1=1Ω, R2=0.02Ω, X2=0.04Ω, a=5. Find Req1 and Xeq1.

Given: R1=0.5, X1=1, R2=0.02, X2=0.04, a=5

  1. Req1 = R1 + a^2*R2 = 0.5 + 25*0.02 = 0.5 + 0.5 = 1.0Ω
  2. Xeq1 = X1 + a^2*X2 = 1 + 25*0.04 = 1 + 1.0 = 2.0Ω
  3. Zeq1 = sqrt(Req1^2 + Xeq1^2) = sqrt(1+4) = sqrt(5) = 2.24Ω

Answer: Req1 = 1.0Ω, Xeq1 = 2.0Ω, |Zeq1| = 2.24Ω

Open Circuit Test (Finds Core Loss Parameters)

R_c = \frac{V_0^2}{P_0}, \quad X_m = \frac{V_0}{I_m}, \quad I_m = \sqrt{I_0^2 - I_c^2}

SymbolDescriptionUnit
V0Rated voltage applied (LV side)V
P0No-load power loss (core loss)W
I0No-load currentA
RcCore loss resistanceΩ
XmMagnetising reactanceΩ

Worked example

OC test on LV side: V0=230V, I0=1.2A, P0=100W. Find Rc and Xm.

Given: V0=230V, I0=1.2A, P0=100W

  1. Rc = V0^2 / P0 = 230^2 / 100 = 52,900 / 100 = 529Ω
  2. Power factor of no-load: cosφ0 = P0/(V0*I0) = 100/(230*1.2) = 100/276 = 0.362
  3. Ic = I0 * cosφ0 = 1.2 * 0.362 = 0.435A
  4. Im = sqrt(I0^2 - Ic^2) = sqrt(1.44 - 0.189) = sqrt(1.251) = 1.118A
  5. Xm = V0/Im = 230/1.118 = 205.7Ω

Answer: Rc = 529Ω, Xm = 205.7Ω

Short Circuit Test (Finds Series Impedance)

Z_{eq} = \frac{V_{sc}}{I_{sc}}, \quad R_{eq} = \frac{P_{sc}}{I_{sc}^2}, \quad X_{eq} = \sqrt{Z_{eq}^2 - R_{eq}^2}

SymbolDescriptionUnit
V_scVoltage at short circuit test (rated current)V
I_scRated current during SC testA
P_scPower input during SC test (copper loss)W

Worked example

SC test on HV side (rated current): V_sc=22V, I_sc=10A, P_sc=150W. Find Zeq, Req, Xeq referred to HV side.

Given: V_sc=22V, I_sc=10A, P_sc=150W

  1. Zeq = V_sc/I_sc = 22/10 = 2.2Ω
  2. Req = P_sc/I_sc^2 = 150/100 = 1.5Ω
  3. Xeq = sqrt(Zeq^2 - Req^2) = sqrt(2.2^2 - 1.5^2) = sqrt(4.84 - 2.25) = sqrt(2.59) = 1.61Ω

Answer: Zeq=2.2Ω, Req=1.5Ω, Xeq=1.61Ω (referred to HV)

Voltage Regulation

Voltage Regulation (Exact)

\%VR = \frac{V_{2,no-load} - V_{2,full-load}}{V_{2,full-load}} \times 100

SymbolDescriptionUnit
V2,nlSecondary no-load voltageV
V2,flSecondary full-load voltageV

Worked example

A transformer secondary gives 230V at no load and 220V at full load. Find % VR.

Given: V2_nl = 230V, V2_fl = 220V

  1. %VR = (230 - 220)/220 * 100
  2. = 10/220 * 100
  3. = 4.55%

Answer: %VR = 4.55%

Approximate Voltage Regulation

\%VR \approx \epsilon_R \cos\phi \pm \epsilon_X \sin\phi

SymbolDescriptionUnit
εRPer-unit resistance drop = IReq/Vpu
εXPer-unit reactance drop = IXeq/Vpu
cosφLoad power factor
+ for lag+ sign for lagging load, - for leading

Worked example

A transformer has εR=0.02 pu, εX=0.04 pu. Load pf=0.8 lagging. Find approximate %VR.

Given: εR=0.02, εX=0.04, cosφ=0.8, sinφ=0.6

  1. For lagging load: %VR = εR*cosφ + εX*sinφ
  2. = 0.02*0.8 + 0.04*0.6
  3. = 0.016 + 0.024
  4. = 0.04 pu = 4%

Answer: %VR = 4% (lagging load)

Efficiency

Transformer Efficiency

\eta = \frac{x \cdot S \cdot \cos\phi}{x \cdot S \cdot \cos\phi + P_i + x^2 P_c} \times 100\%

SymbolDescriptionUnit
xFraction of full load (0 to 1)pu
SFull-load VA ratingVA
PiIron (core) loss, constantW
PcFull-load copper lossW
cosφPower factor of load

Worked example

A 50kVA transformer: Pi=200W, Pc (full load)=500W, pf=0.9. Find η at full load.

Given: S=50000VA, Pi=200W, Pc=500W, cosφ=0.9, x=1

  1. Output power = x*S*cosφ = 1*50000*0.9 = 45000W
  2. Total losses = Pi + x^2*Pc = 200 + 1*500 = 700W
  3. η = 45000/(45000+700) * 100 = 45000/45700 * 100 = 98.47%

Answer: η = 98.47% at full load, pf=0.9

Condition for Maximum Efficiency

P_i = x^2 P_c \Rightarrow x_{m} = \sqrt{\frac{P_i}{P_c}}

SymbolDescriptionUnit
xmFraction of full load at maximum efficiencypu

Worked example

A transformer: Pi=200W, Pc=500W. At what load fraction does maximum efficiency occur?

Given: Pi=200W, Pc=500W

  1. xm = sqrt(Pi/Pc) = sqrt(200/500)
  2. = sqrt(0.4)
  3. = 0.632
  4. So maximum efficiency occurs at 63.2% of full load

Answer: xm = 0.632 (63.2% of full load)

All-Day Efficiency

\eta_{all-day} = \frac{\text{Energy output (kWh)}}{\text{Energy output + Total energy losses}} \times 100\%

SymbolDescriptionUnit
Energy outputkWh output over 24 hourskWh
Total lossesIron losses × 24h + copper losses × hours at each loadkWh

Worked example

A distribution transformer: Pi=100W. Operates 8h at full load (10kVA, pf=0.8, Pc_fl=250W) and 16h at no load. Find all-day efficiency.

Given: Pi=100W, S=10kVA, cosφ=0.8, Pc_fl=250W, 8h full load, 16h no load

  1. Energy output = 10000*0.8*8 = 64,000Wh = 64kWh
  2. Iron loss energy = 0.1kW * 24h = 2.4kWh
  3. Copper loss energy = 0.25kW * 8h = 2kWh (only when loaded)
  4. Total loss energy = 2.4 + 2.0 = 4.4kWh
  5. η_all-day = 64/(64+4.4) * 100 = 64/68.4 * 100 = 93.57%

Answer: η_all-day = 93.57%

Per-Unit System

Per-Unit Quantities

Z_{pu} = \frac{Z_{actual}}{Z_{base}}, \quad Z_{base} = \frac{V_{base}^2}{S_{base}}

SymbolDescriptionUnit
Z_puPer-unit impedancepu
V_baseBase voltageV
S_baseBase apparent powerVA

Worked example

A 100kVA, 11kV/400V transformer has Zeq=2.5Ω referred to LV side. Find Z_pu on LV base.

Given: S_base=100,000VA, V_base=400V, Z_actual=2.5Ω

  1. Z_base = V_base^2 / S_base = 400^2 / 100,000 = 160,000/100,000 = 1.6Ω
  2. Z_pu = Z_actual / Z_base = 2.5 / 1.6 = 1.5625 pu
  3. This is a high leakage impedance — typical for a current-limiting transformer

Answer: Z_pu = 1.5625 pu (on LV base)

Change of Base Formula

Z_{pu,new} = Z_{pu,old} \times \frac{S_{base,new}}{S_{base,old}} \times \left(\frac{V_{base,old}}{V_{base,new}}\right)^2

SymbolDescriptionUnit
Z_pu,newPer-unit impedance on new basepu
S_base,newNew MVA baseVA
V_base,newNew voltage baseV

Worked example

Transformer Z_pu=0.05 pu on 100kVA, 11kV base. Convert to 200kVA, 11kV base.

Given: Z_old=0.05pu, S_old=100kVA, S_new=200kVA, V same

  1. Z_pu,new = Z_pu,old * (S_new/S_old) * (V_old/V_new)^2
  2. = 0.05 * (200/100) * (1)^2
  3. = 0.05 * 2 = 0.10 pu

Answer: Z_pu,new = 0.10 pu on 200kVA base

Three-Phase Transformer Connections

Turns Ratio for Three-Phase Transformers

a = \frac{N_1}{N_2} = \frac{V_{1L}/\sqrt{3}}{V_{2L}/\sqrt{3}} \text{ (Y-Y)}, \quad a = \frac{V_{1L}/\sqrt{3}}{V_{2L}} \text{ (Y-Δ)}

SymbolDescriptionUnit
V1L, V2LPrimary and secondary line voltagesV

Worked example

A Y-Δ transformer: V1L=11kV (Y), V2L=415V (Δ). Find the turns ratio of each single-phase unit.

Given: V1L=11000V (star), V2L=415V (delta)

  1. Primary phase voltage (star): V1P = 11000/sqrt(3) = 6350V
  2. Secondary phase voltage (delta): V2P = V2L = 415V
  3. Turns ratio a = V1P/V2P = 6350/415 = 15.3

Answer: Turns ratio a = 15.3 per single-phase unit

Scott Connection (3-phase to 2-phase)

\text{Teaser turns} = \frac{\sqrt{3}}{2} N, \quad \text{Main turns} = N

SymbolDescriptionUnit
NNumber of turns in main transformerturns

Worked example

A Scott connection uses main transformer with 1000 turns on the primary. How many turns does the teaser transformer need?

Given: N_main = 1000 turns

  1. Teaser turns = (sqrt(3)/2) * N_main
  2. = 0.866 * 1000
  3. = 866 turns
  4. The centre tap is at 500 turns from the main transformer

Answer: Teaser primary turns = 866

Quick reference

FormulaExpression
EMF EquationE = 4.44·f·N·Φm
Turns Ratioa = N1/N2 = V1/V2 = I2/I1
Impedance TransformationZ_reflected = a²·Z2
Req referred to primaryReq1 = R1 + a²R2
OC Test: RcRc = V0²/P0
OC Test: XmXm = V0/Im; Im=√(I0²-Ic²)
SC Test: ZeqZeq = Vsc/Isc
SC Test: ReqReq = Psc/Isc²
Efficiency at load xη = x·S·cosφ / (x·S·cosφ + Pi + x²Pc)
Max efficiency conditionPi = x²·Pc → xm = √(Pi/Pc)
Voltage Regulation%VR = (V_nl - V_fl)/V_fl × 100
Approx %VRεR·cosφ ± εX·sinφ
Per-unit base impedanceZbase = Vbase²/Sbase
Change of baseZpu_new = Zpu_old × (Snew/Sold) × (Vold/Vnew)²
Delta-Star turns ratioa = (V1L/√3)/V2L for Y-Δ

Exam tips

  • GATE repeatedly tests the OC and SC test analysis — the OC test gives core loss parameters (Rc, Xm) performed on the LV side, while the SC test gives series impedance (Req, Xeq) performed on the HV side at rated current.
  • The condition for maximum efficiency is iron loss equals copper loss (Pi = x²Pc) — examiners often give Pi and Pc and ask for the load at which η_max occurs; use xm = √(Pi/Pc).
  • Voltage regulation sign matters — lagging loads give positive (poor) regulation and leading loads can give negative regulation; the approximate formula εR·cosφ ± εX·sinφ with + for lag is frequently tested.
  • In per-unit calculations, always convert all quantities to the same base before performing any analysis; the change-of-base formula is essential when manufacturers specify impedance on their own nameplate rating.
  • All-day efficiency is specifically relevant to distribution transformers and tests whether you account for iron losses over 24 hours even at no load — a common trap is forgetting to add no-load iron loss for the unloaded hours.